FSP-23-R
AI

The **FSP-23-R** (commonly referred to as the FSP-2 series) is a high-performance, passive infrared (PIR) occupancy sensor typically used in high-bay lighting applications. It is designed to provide multi-level control based on motion and daylight contribution.
---
### Core Electronic Components and Specifications
The device integrates several electronic sub-systems to manage power and environmental sensing.
| Component | Description | Specification/Function |
| :--- | :--- | :--- |
| **PIR Sensor** | Fresnel lens coupled with a pyroelectric detector | Detects infrared energy changes (motion). |
| **Photosensor** | Integrated light-level sensor | Measures ambient light for "daylight harvesting." |
| **Microcontroller** | Internal Logic Unit | Processes timing, sensitivity, and dimming curves. |
| **Dimming Interface** | 0-10V DC Control lines | Connects to LED drivers or electronic ballasts. |
| **Relay** | Internal Electromechanical Switch | Switches the primary AC load ON/OFF. |
---
### Functional Electronic Features
#### 1. Power Supply and Voltage Handling
The FSP-23-R is designed to operate across a wide range of industrial voltages.
* **Operating Voltage:** 100–347VAC (single phase).
* **Frequency:** 50/60Hz.
* **Load Ratings:**
* @ 120V: 0-800W Tungsten/Ballast/LED.
* @ 277V: 0-1200W Ballast/LED.
* @ 347V: 0-1500W Ballast/LED.
#### 2. Dimming Control (0-10V)
The sensor acts as a current sink for the 0-10V dimming signal provided by the LED driver.
* **Low Mode:** 0V to 9.8V (customizable).
* **High Mode:** 10V (full brightness).
* **Fade Times:** Electronically controlled ramp-up and ramp-down to prevent sudden light flashes.
#### 3. Communication Interface
Unlike traditional sensors with physical dials, the FSP-23-R uses an **Infrared (IR) Transceiver**.
* **Programming:** Settings are adjusted via the **FSIR-100** wireless handheld tool.
* **Storage:** Parameters are stored in non-volatile memory (EEPROM), meaning settings are retained during a power outage.
---
### Wiring Color Codes
To integrate the FSP-23-R into a circuit, the following lead wires are used:
```yaml
Power_Wires:
Line: Black
Load: Red
Neutral: White
Control_Wires:
Dim_Positive: Violet (+10VDC)
Dim_Negative: Gray/Pink (Common)
```
---
### Detection Performance
The electronic sensitivity is categorized by the lens installed:
* **FSP-L2:** 360° coverage at 8ft height (approx. 48ft diameter).
* **FSP-L3:** 360° coverage at 20ft height (approx. 40ft diameter).
* **FSP-L7:** 360° coverage at 40ft height (approx. 100ft diameter).
- ⤷What is the maximum mounting height for the FSP-23-R?
- ⤷ How do I program the time delay using the FSIR-100 tool?
- ⤷ Can the FSP-23-R be used with 480V circuits?