M2AC-AA4W-R2
AI

The **M2AC-AA4W-R2** is a specific part number belonging to the **M2 Series** of Signal Conditioners manufactured by **M-System** (now often branded under **MG CO., LTD.**). These devices are used in industrial automation to convert, isolate, and transmit electrical signals.
Below is a breakdown of the electronic specifications and characteristics based on the part number nomenclature.
---
### 1. Part Number Deciphering
The alphanumeric code indicates the specific hardware configuration of the module:
| Segment | Code | Description |
| :--- | :--- | :--- |
| **Series** | M2 | M2 Series Signal Conditioner (Plug-in base) |
| **Model** | AC | AC Transmitter (converts AC voltage/current to DC) |
| **Input** | AA | 0 – 5 A AC (Current Input) |
| **Output** | 4W | 4 – 20 mA DC (Current Output) |
| **Power Supply**| R2 | 110V AC / 220V AC (Selectable) |
---
### 2. Key Electronic Components & Functions
The internal circuitry of this device is designed for high-precision industrial environments. Key electronic features include:
* **CT (Current Transformer) Input:** Since the input is 5A AC, the device contains an internal step-down transformer or a precision shunt to sample high AC current safely.
* **Galvanic Isolation:** This module provides **three-way isolation** (Input to Output to Power). This prevents ground loops and protects sensitive PLC/DCS inputs from high-voltage surges on the AC line.
* **AC-to-DC Conversion (Rectification):** The electronic core converts the AC sinusoidal wave into an RMS-calibrated or average-sensing DC signal.
* **Zero/Span Adjustment:** On the front panel, there are typically two potentiometers (trimmer resistors) that allow for fine-tuning the 4mA (zero) and 20mA (span) output points.
---
### 3. Technical Specifications
Typical performance metrics for the M2AC series:
| Parameter | Specification |
| :--- | :--- |
| **Accuracy** | ±0.3% of span |
| **Response Time** | ≤ 0.5 seconds (0 – 90%) |
| **Insulation Resistance** | 100 MΩ or more (500V DC) |
| **Isolation Strength** | 2000V AC @ 1 minute |
| **Load Resistance** | Max 750 Ω for 4-20mA output |
| **Frequency Range** | 40 Hz to 1 kHz |
---
### 4. Wiring Diagram Overview
The device uses a **socket-mount (8-pin or 11-pin)** base.
```text
Input (AC 5A): Terminals 1 & 8
Output (4-20mA): Terminals 4(+) & 5(-)
Power Supply: Terminals 2 & 3
```
*(Note: Always verify with the specific wiring label on the side of the actual unit before energizing.)*
---
- ⤷What is the difference between RMS sensing and average sensing for this model?
- ⤷ Can this unit be mounted on a standard DIN rail?
- ⤷ What are the power consumption ratings for the R2 power option?