M2RTS-R-C3-M2/N
AI

The **M2RTS-R-C3-M2/N** is a specific configuration of a high-performance **Signal Conditioner** (specifically a Resistance Temperature Detector or RTD transmitter) manufactured by **M-System**.
This device is designed to convert signals from an RTD sensor into a standard industrial DC signal (like 4-20mA or 0-10V).
---
### 1. Model Code Breakdown
Understanding the electronic capabilities of this unit requires deconstructing the model number:
| Code Segment | Description | Technical Specification |
| :--- | :--- | :--- |
| **M2RTS** | Series Name | Mini-M Series RTD Transmitter |
| **-R** | Power Input | 24V DC (Allowable range: 24V ±10%) |
| **-C3** | Input Type | Cu 10 Ω @ 25°C (Copper RTD sensor) |
| **-M2** | Output Type | 4 – 20 mA DC (Current output) |
| **-N** | Option | No Special Options (Standard configuration) |
---
### 2. Key Electronic Components & Functions
The internal circuitry of the M2RTS is divided into several functional stages:
#### A. Input Circuit (Sensor Interface)
* **Constant Current Source:** Since it interfaces with a Cu 10Ω RTD, the device sends a small, stable current through the sensor to measure resistance changes.
* **Linearization Circuit:** RTD resistance change is not perfectly linear relative to temperature. This electronic stage corrects the curve to ensure the output is proportional to the temperature.
* **Burnout Protection:** Includes a circuit to detect if a sensor wire is broken. If detected, the output will typically drive to a "High" (upscale) or "Low" (downscale) limit.
#### B. Isolation Barrier
* **Three-Way Isolation:** The electronic architecture provides 2000V AC isolation between the **Input**, **Output**, and **Power** terminals. This prevents ground loops and protects sensitive PLC/DCS hardware from electrical surges on the sensor side.
#### C. Output Stage
* **Current Driver:** Converts the processed signal into a precise 4-20mA DC loop.
* **Zero/Span Adjustments:** Located on the front panel, these allow for electronic calibration to fine-tune the minimum (4mA) and maximum (20mA) points.
---
### 3. Electronic Specifications
| Parameter | Specification |
| :--- | :--- |
| **Power Consumption** | Approx. 3W |
| **Response Time** | ≤ 0.5 seconds (0 – 90%) |
| **Isolation Resistance** | ≥ 100 MΩ with 500V DC |
| **Dielectric Strength** | 2000V AC @ 1 minute |
| **Load Resistance** | Max 550 Ω |
---
### 4. Terminal Configuration (Wiring)
| Terminal | Function |
| :--- | :--- |
| **1 - 2** | Output (+) and (-) |
| **3 - 4** | Power Supply (24V DC) |
| **5 - 6 - 7** | RTD Input (A, B, B') |
- ⤷