M2RTS-S-DF-R2/UL
AI

The **M2RTS-S-DF-R2/UL** is a specialized electronic signal conditioner and transmitter produced by **M-System** (now part of MG CO., LTD). It is primarily used in industrial automation and process control to convert resistance signals from sensors into standard DC voltage or current signals.
### 1. General Specifications
This device is a high-performance, plug-in signal conditioner designed for rail mounting.
| Feature | Specification |
| :--- | :--- |
| **Model Series** | M2 Series (Mini-M) |
| **Input Type** | RTD (Resistance Temperature Detector) or Potentiometer |
| **Output Type** | DC Voltage or Current (Standardized) |
| **Construction** | Plug-in style with base socket |
| **Isolation** | 3-way isolation (Input, Output, Power) |
| **Safety Approvals** | UL/cUL recognized |
---
### 2. Breakdown of the Part Number
The alphanumeric code describes the specific hardware configuration:
| Code Segment | Meaning | Details |
| :--- | :--- | :--- |
| **M2RTS** | Model Category | RTD Transmitter |
| **S** | Output Type | Current output (typically 4–20mA DC) |
| **DF** | Input Type | DIN (Pt 100) or specific resistance range |
| **R2** | Power Input | 24V DC (approx. ±10% range) |
| **UL** | Certification | UL/cUL Standard Approval |
---
### 3. Key Electronic Functions
#### A. Signal Conversion
The unit takes the ohmic resistance value from an RTD (like a Pt100) and converts it into a linear 4-20mA signal. This allows temperature data to be sent over long distances to a PLC or DCS without signal degradation caused by wire resistance.
#### B. 3-Way Isolation
The device electronically separates the input circuit, the output circuit, and the power supply.
* **Purpose:** Prevents ground loops, protects sensitive downstream equipment from high-voltage surges, and reduces electromagnetic interference (EMI).
#### C. Linearization
RTD sensors are not perfectly linear. The internal electronics of the M2RTS-S-DF-R2/UL apply a linearization curve to ensure the output current is precisely proportional to the temperature, not just the raw resistance.
---
### 4. Technical Data Sheet Summary
* **Accuracy:** Typically ±0.1% to ±0.2% of span.
* **Response Time:** ≤ 0.5 seconds (0 to 90%).
* **Insulation Resistance:** 100 MΩ or more with 500V DC.
* **Dielectric Strength:** 2000V AC @ 1 minute (Input to Output to Power to Ground).
* **Housing Material:** Flame-resistant resin (Black).
---
- ⤷
What are the wiring diagrams for the M2RTS base socket?
- ⤷ How do I calibrate the zero and span settings on this unit?
- ⤷ Can this transmitter be used with Pt1000 sensors or only Pt100?