Applications ■ Use Part No. 314 to electrically connect two or three wire ends, insulate the connection, and provide a moisture resistant seal. Wire Range 22-14 AWG Solid or stranded, tinned or untinned (0,5-1.5 mm2) copper conductors. For use with common thermoplastic insulated wires: T, TF, TFF, TFN, TFFN, AWM, TEW, SAE-GPT with a maximum insulation diameter of .150 inches (3,8 mm). Maximum recommended current for general purpose applications: 22 AWG - 3 AMPS, 20 AWG - 5 AMPS, 18 AWG - 7 AMPS, 16 AWG - 10 AMPS, 14 AWG - 15 AMPS. Construction U-contact - Tin plated brass, .02 in. (0,5 mm) thick Insulator - Flame retardant nylon, Color - cap/dk. blue, body/white Sealant - Mineral Oil Base EG-3 Grease Weight .0077 lb. (3,49 gm) Recommended Installation Tools 3M™ Crimping Tool No. E-9BM Mechanics (slip joint) Pliers Installation Instructions 1. Insert 2 or 3 unstripped wires completely into connector and check their position by looking through the translucent connector body. 2. Hold tool perpendicular to the wires and make the connection by driving the cap down flush with the top edge of the connector body. Regulatory Agencies UL Listed - Tested per UL Standard 486C UL file No. E23438 CSA certified - CSA Std. C22.2 No. 0. 188-MI983 CSA File No. LR15503 (Voltage rated at 600 volts maximum, building wire: 1000 volts maximum, signs, fixtures and luminaires. Operating Temperature: 105˚C.)
|