DMS-20LCD-4/20S-C. Datasheet(PDF) 4 Page - Murata Power Solutions Inc.

Part # DMS-20LCD-4/20S-C.
Description  4-20mA Input Loop-Powered Ultra-Low 1.8V Loop Drop 3쩍 Digit LCD Display Process Monitors
PDF  6 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
Manufacturer  MURATA-PS [Murata Power Solutions Inc.]
Direct Link  http://www.murata-ps.com
Logo MURATA-PS - Murata Power Solutions Inc.

DMS-20LCD-4/20S-C. Datasheet(HTML) 4 Page - Murata Power Solutions Inc.

  DMS-20LCD-4/20S-C. Datasheet HTML 1Page - Murata Power Solutions Inc. DMS-20LCD-4/20S-C. Datasheet HTML 2Page - Murata Power Solutions Inc. DMS-20LCD-4/20S-C. Datasheet HTML 3Page - Murata Power Solutions Inc. DMS-20LCD-4/20S-C. Datasheet HTML 4Page - Murata Power Solutions Inc. DMS-20LCD-4/20S-C. Datasheet HTML 5Page - Murata Power Solutions Inc. DMS-20LCD-4/20S-C. Datasheet HTML 6Page - Murata Power Solutions Inc.  
Zoom Inzoom in Zoom Outzoom out
 4 / 6 page
background image
Table 4. Decimal Point Settings
Examples (DMS-20LCD-4/20P-Positive Model)
1. Desired display readings are:
4mA = “650”
20mA = “950”
Use DIP-switch setting #4 in Table 3 since subtracting 650 from 950 yields
a differential value of 300. Apply 4mA and adjust R3 until the display reads
“000”. Apply 20mA and adjust R7 until the display reads “300” (the differen-
tial value previously calculated). Apply 4mA and adjust R3 until the display
reads “650”. Apply 20mA and verify that the display reads “950”.
2. Desired display readings are:
4mA = “4.00”
20mA = “19.99”
This example illustrates the DMS-20LCD-4/20P’s capability to display higher
differential readings than those indicated in Table 3. This example also
illustrates how the DMS-20LCD-4/20P can be used to display the output
levels of a 4-20mA loop transmitter with higher precision (0.01mA versus
0.1mA) than described above.
Subtracting 400 from 1999 yields a differential of 1599, a value not listed in
Table 3. However, use DIP-switch setting #1 in Table 3 since this setting has
the highest overall offset/span adjustment capabilities. Enable DP2 via SW5
then apply 4mA and adjust R3 so the display reads “0.00”. Apply 20mA and
adjust R7 so the display reads “15.99”. Apply 4mA and adjust R3 until the
display reads “4.00”. Apply 20mA and check to see that the display reads
“19.99” or just overranges (“1—“). Repeat adjustment procedure if neces-
sary.
Table 3. DMS-20LCD-4/20P (Pos. Reading) DIP-Switch Settings
Differential Range
4mA Input
20mA Input
Display Reading
SW1
SW2
SW3
SW4
SW5
SW6
DP1
DP2
DP3
1. 800-1400
900
1700
Off
Off
Off
2. 500-800
850
1350
On
Off
Off
3. 350-500
800
1150
Off
On
Off
4. 250-350
750
1000
Off
Off
On
5. 150-250
750
900
On
On
On
1
2
3
4
56
ON
12
3
4
5
6
ON
The first step when configuring the DMS-20LCD-4/20P for the first time, or
when selecting a new range, is to set R3 fully counterclockwise and R7 fully
clockwise (roughly 22 turns) to their minimum offset/minimum span posi-
tions, respectively.
The next step is to calculate the required display differential-reading; this
is accomplished by subtracting the desired 4mA display reading from the
desired 20mA display reading, disregarding decimal points. Then, using the
calculated differential display-reading to select the appropriate DIP-switch
setting # from Table 3, configure DIP-switches SW1, SW2, and SW3 accord-
ingly. Make certain that the DIP-switch’s small actuators are firmly engaged
in their fully-ON or fully-OFF positions.
The procedure below describes how to calibrate the meter for an application
which the DMS-20LCD-4/20P easily accommodates: displaying the output
of a 4-20mA transmitter, that is, "04.0" with a 4mA input and "20.0" with a
20mA input.
1. Set R3 fully counterclockwise (minimum offset position) and R7 fully
clockwise (minimum differential span position), roughly 22 turns.
2. Subtract 040 from 200 to yield a differential value of 160; use
this value to select DIP-switch setting #5 in Table 3. Enable decimal
point DP3 by placing SW6 to the ON position.
3. Set the transmitter’s output to 4.0mA and carefully adjust R3 clockwise
until the meter’s display reads “000”.
4. Set the transmitter’s output to 20.0mA and adjust R7 counterclock-
wise until the meter’s display reads “16.0”.
5. Set the transmitter back to 4.0mA and slowly adjust R3 clockwise until
the display reads “04.0”. Reapply 20.0mA and the display should now
read “20.0”. Repeat steps 3, 4 and 5 to make sure the adjustments did
not affect one another.
DMS-20LCD-4/20 Series
4-20mA Input Loop-Powered Ultra-Low 1.8V Loop Drop
3½ Digit LCD Display Process Monitors
MPM_DMS20LCD-420.B02 Page 4 of 6
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000
www.murata-ps.com



Html Pages

1 2 3 4 5 6


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com