| Electronic Components Datasheet Search |
|
B75-1B20-JDG Datasheet(PDF) 4 Page - Magnetrol International, Inc. |
|
|
|||||||||||||||||||||||||||||
B75-1B20-JDG Datasheet(HTML) 4 Page - Magnetrol International, Inc. |
|
4 / 8 page ![]() 3.0 Reversing Pilot Action All Series J Pneumatic Switch Mechanisms are shipped from the factory set-up for direct action; closed at high level. They can be field modified for the reverse (open) position by following the steps below: 1. First remove the upper shoulder screw from the actuator link and move it from the direct (D) position to the reverse (R); refer to Figure 3. 2. Loosen the screw that positions the spring bracket and move it from the direct (D) position to the reverse (R) position; refer to Figure 4. 3. Fasten screw securely. The switch is now setup for reverse action. 4 42-685 Series J Pneumatic Switch Mechanism Figure 4 Fall out spring Reverse position Enclosing tube Direct position Air line adapter Spring bracket Reverse position Upper shoulder screw Actuator link Air line adapter Enclosing tube Direct position Figure 3 |
|
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |