Back Button 3G5A2-RPT01-E Datasheet HTML 88Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 89Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 90Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 91Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 92Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 93Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 94Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 95Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 96Page - Omron Electronics LLC Next Button
Zoom Inzoom in Zoom Outzoom out
 92 / 182 page
background image
79
Non-fatal Errors
Item
Cause
CPU indicators
Peripheral
Device error
Power
RUN ERROR WDT ALARM OUT INT
COMM
message
System error
(FAL)
Program has ex-
ecuted FAL
Lit
Lit
Unlit
Unlit
Lit
---
---
SYSTEM ERR
FAL
JMP error
Destination of JMP/
CJP/CJPN is miss-
ing.
Lit
Lit
Unlit
Unlit
Lit
---
---
JMP ERR
Indirect DM
BCD error
Data for indirectly
addressed DM is
not BCD.
Lit
Lit
Unlit
Unlit
Lit
---
---
INDIRECT DM
BCD ERR
Non-fatal SFC
error
Error has occurred
during SFC execu-
tion.
Lit
Lit
Unlit
Unlit
Lit
---
---
SFC CONTIN-
UE
ERR
I/O verification
error
I/O table contains a
different number of
I/O points than is
actually mounted.
Lit
Lit
Unlit
Unlit
Lit
---
---
I/O VERIFY
ERR
CPU Bus Unit
error
Parity error occurs
during data transfer
between CPU and
CPU Bus Unit.
Lit
Lit
Unlit
Unlit
Lit
---
---
CPU SPECIAL
UNIT ERR
SYSMAC
BUS/2 error
Error occurs be-
tween Master and
Slave in SYSMAC
BUS/2.
Lit
Lit
Unlit
Unlit
Lit
---
---
SYSMAC
BUS/2 ERR
SYSMAC BUS
error
Error occurs be-
tween Master and
Slave in SYSMAC
BUS.
Lit
Lit
Unlit
Unlit
Lit
---
---
SYSMAC BUS
ERR
Battery failure
Battery of CPU or
Memory Card is not
connected or bat-
tery voltage is low.
Lit
Lit
Unlit
Unlit
Lit
---
---
BATTERY ERR
CPU Bus Unit
setting error
Number assigned
to CPU Bus Unit
does not agree with
registered unit
number.
Lit
Lit
Unlit
Unlit
Lit
---
---
CPU SPECIAL
UNIT SETTING
ERR
Momentary
power interrup-
tion
Momentary power
interruption oc-
curred (when spe-
cified as error by in
PC Setup)
Lit
Lit
Unlit
Unlit
Lit
---
---
PROTECTED
Output inhibit
(*)
Bit A00015 is ON.
Lit
Lit
Unlit
Unlit
---
Lit
---
---
Host link com-
munication
Error has occurred
during host link
communication
Lit
Lit
Unlit
Unlit
---
---
Lit
---
Note *All outputs of the I/O Units are turned OFF.
Error Messages and Alarm Outputs
Section 5-1



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100  ...More


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com