32 / 80 page ![]() 1 Insulated wire 3 -48V + RTN lug 5 1/2” 2 Heat-shrink tubing 4 1/4” 6 5/8” • Figure 21: Ground Lug Wiring Termination (PWR-2700W-DC-R) 1 Insulated wire 3 5/16” Ø 2 Ground lug (right angle) 4 Heat-shrink tubing 2. Use agency-approved compression (pressure) lugs for wiring terminations with a single 5/16" mounting hole. Two-hole lugs should have 1/4" mounting holes on 5/8" centers. The PWR-2700W-DC-R ground lug is a right-angle lug. Check the terminations for the appropriate wire size. Use a ground wire of at least 2 – 4 AWG. Use only copper wire. 3. Slip on heat-shrink tubing on the wire ends before assembling the lugs on to the wire. • The lugs must be crimped with the proper tool. • The tubing should extend over the lug’s barrel and the wire's insulator. 4. Shrink the tubing with a heat gun. 4.4.3 PWR-3K-DC-RED Power Supply Figure 22: PWR-3K-DC-RED Power Supply displays the PWR-3K-DC-RED power supply. 28 |
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|