70 / 182 page ![]() 57 3-4-4 Emergency Stop You can use an external relay (CR in the following figure) to form an emergency stop circuit that shuts down the system when PC operation stops. This can be achieved by wiring the RUN output from the Power Supply Unit on the CPU Rack as shown below. MCB1 MCB2 CR1 Power supply Control section DC voltage regulator Transformer or noise filter Twisted-pair wires PC RUN output + – DC input/output CR1 Surge suppressor PC 3-4-5 Power Interruptions A sequence circuit is built into the PC to handle power interruptions. This circuit prevents malfunctions due to momentary power loss or voltage drops. A timing diagram for the operation of this circuit is shown below. Power supply Power interrup- tion detection signal Program execution Momentary Power Interruption Flag (A40202) CPU reset signal RUN output *0.3 to 1 ms for DC power. 85% Power interruption power interruption detection time: 10 to 25 ms* Shutdown processing Momentary power inter- ruption time (default: 0 ms) Initialization Normal Normal Stops Standby Power retention time: 10 ms (fixed) Power OFF interrupt program Power-ON interrupt program Power Supply Units Section 3-4 |
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |