Back Button 822-1002-C01 Datasheet HTML 18Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 19Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 20Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 21Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 22Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 23Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 24Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 25Page - Magnetrol International, Inc. 822-1002-C01 Datasheet HTML 26Page - Magnetrol International, Inc. Next Button
Zoom Inzoom in Zoom Outzoom out
 22 / 40 page
background image
Probe
high
Probe low
Figure 14
3. Press the DOWN
arrow key to get to MODE. Press
ENT
.
4. Scroll to SING. Press ENT
. Unit reads NOT READY.
You are now in the Single Point Mode.
5. Return to CNFG and repeat the above procedure now
choose MULT from the MODE menu. Press ENT
. Unit
reads MAGNETROL INTL M M M….
6. All of the original data has now been cleared.
7. Begin Probe Calibration procedure again from the start of
Program Path 3 (page 17).
2.4.2.2 Error Messages in PRLO/HI Menus
1. 2BIG: Occurs during PRLO or PRHI data entry when
displayed value exceeds 19999.
2. 2SML: Occurs during PRLO data entry when displayed
value underflows 0, or during PRHI when displayed value
underflows 1.
3. 2 LO: Occurs when stored PRHI measurement (not
display) would be less than currently stored PRLO
measurement. In other words, the capacitance being
used to set the PRHI point is less than the capacitance
used to set the PRLO.
4. 2 HI: Occurs when stored PRLO measurement (not
display) would be more than currently stored PRHI
measurement. In other words, the capacitance being
used to set the PRLO point is more than the capacitance
used to set the PRHI point.
5. UNDR: Occurs when displayed value goes below -999.
6. OVER: Occurs when displayed value goes above 19,999
(red, >10,000 LED illuminated and 9999 on the display).
ENT
ENT
ENT
50-621 Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches
19



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com