51 / 118 page ![]() 41 T1000 Series UPS 5.6-6kVA Installation and Operation Manual – 91074-005 14. Operation 14.1 Cold Start Cold Start is the process of starting a UPS up in backup mode in the absence of Utility power. To cold start the T1000, perform the following steps: NOTE: If the unit is configured for frequency auto-detect (the default shipping mode), the default out- put frequency for a cold start is 60Hz. 1. Ensure the battery module(s) are plugged in. 2. Ensure the Input/Utility power to the UPS is disconnected. 3. Disconnect the load from the UPS output when performing a cold start. If this is not possible, en- sure the load does not exceed the rated output of the UPS. 4. Close the MCCB1 circuit breaker located on the back of the UPS. NOTE - Ensure the input voltage is set to less than or equal to the output voltage. 5. Press (no holding required) the cold start button located opposite the front panel display. It is par- tially obscured by the handle recess. (Fig. 14-1) 6. The transition from Cold Start to Online is automatic once the utility power is connected. NOTE: After starting in Cold Start, if you press START/STOP while still in backup (before utility power is restored) the unit will go into shutdown. 14.2 EPO and Remote Stop There are two terminal blocks, designated EPO and Rem. Stop, for connecting switches to the UPS to allow remotely (100 m) Stopping or Shutting Down the UPS by pressing a switch. (See Fig. 14-2) EPO (Emergency Power Off) The EPO is triggered by an external switch. The EPO terminals provide 208/240Vac (same as UPS output terminals). The external switch should be rated for a minimum of 300Vac and 300mA. When the EPO switch is closed, the Input circuit breaker to the UPS opens and all power to the unit is removed, including backup power from the batteries. NOTE: EPO operation should be limited to no more than 4 operations per minute, and no more than 24 operations per hour. Exceeding this duty cycle will overheat the EPO circuits. FIGURE 14-1: COLD START SWITCH LOCATION Cold Start Switch Handle Recess |
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |