18 / 118 page ![]() 8 T1000 Series UPS 5.6-6kVA Installation and Operation Manual – 91074-005 5. Installation Precautions NOTICE 1. Observe the following environmental restrictions: • Install the unit in a well-ventilated location. • Install the unit where the ambient temperature is within the range specified in Appendix A - “Specifications”. • DO NOT install the UPS in areas that are subject to high humidity. • DO NOT install the UPS in areas that allow exposure to direct sunlight. • DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or flammable gases. • DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground will reduce the effects of electrical noise and will reduce the potential for electrical shock. • DO NOT install the UPS in areas that would allow fluids or any foreign object to get inside the UPS. 2. Install the unit in a stable, level and upright position that is free of excessive vibration. 3. Follow the instructions on the unpacking label affixed to the exterior of the UPS. 4. Tower Unit with Caster Kit Option Only: Once the installation is complete, screw down the UPS leveling feet located next to the front and back casters, until the unit is no longer resting on the casters. 5. The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a different source than that of the affected equipment. 6. It is the responsibility of the installer of this equipment to provide a suitable disconnect for the Control Panel supplying power to this equipment. This disconnect must: Be suitable for the Voltage and Full Load Ampere Rating of all downstream equipment supplied by the Panel; The supply disconnecting device shall be one of the following types: • Switch-disconnect, with or without fuses, in accordance with IEC 60947-3, utilization category AC-23B or DC-23B • As above, except one that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnect. • A circuit breaker suitable as an isolation device per IEC 60947-2 • Any other switching device in accordance with an IEC product standard that also meets the isolation requirements of IEC 60947-1 and is appropriate for on-load switching of motors or other inductive loads; Be approved for use as a disconnect for the country in which this equipment is installed. Be provided with a Lock Out Tag Out capability in the Off (Down) position. |
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |